Mätsystem för effektförluster i en högfrekvenstransformator


To measure losses in a transformer with today?s methods is either slow or insecure. There s a new method developed by Alstom that hasn't been actualize in to a test-system and that has been the assignment in this project. The idea is built on a switched system and a CLR- circuit in the resonant frequency. The test-system has a calculated power-loss that make the efficiency to be as high as 99,8% and in reality over 95%. But in the end it was discovered that the circuit was only able to deliver 70A when the thought was 200 A. More over was with the frequency of 200 kHz the signal was so distorted that all results over 100 kHz should be questioned. The goal was a efficiency of 99%. That was one of the basis in our calculation and dimensioning. When we order the components we foundbetter than we needed och the efficiency was improved. In the reality the efficiency is 95% and we think it's because the measurements-instruments accuracy and the distortion. In some measurements the efficiency went over 100% and that greatly improve that idea. Every part of the circuit was simulated piece bye piece and then together. That to increase the understanding of the system and to see that themodel works. The simulated efficiency was very low compared to calculated and in reality. The fact was gathered from literature, technical reports from Alstom and meetings with Per Ranstad et. al.