Sökresultat:
1 Uppsatser om Driftbesiktning - Sida 1 av 1
Flygbesiktning av Luftledningar : Modellering av samband mellan besiktningsanmärkningar och systemtillförlitlighet
This paper thoroughly investigates needs and requirements for overhead distribution feeder inspection and develops models to investigate possible relations between short term inspections remarks and outages. The study was conducted in collaboration with Fortum Distribution AB that supplied extensive information about their overhead power feeders concerning both inspection and power outages. The investigated models where lognormal linear model, Poisson generalized linear model and negative binomial generalized linear model. All models were implemented utilizing offset terms to compensate for differences in feeder length and amount of overhead versus underground feeders. The Poisson generalized linear model was rejected at an early stage due to overdispersion and neither of the remaining models fit the data perfectly.